Warning Cookies are used on this site to provide the best user experience. If you continue, we assume that you agree to receive cookies from this site. OK, I agree

Meter of parameters of the loop "phase-zero", "phase-phase" IFN-300

Write a review
39 072.00 
127998
On backorder
+

Using the IFN-300 device, it is possible to measure the resistance of the "phase-zero", "phase-phase" loop and the transition resistance of contact connections. Using the data obtained, it is possible to identify malfunctions in group lines and carry out a set of measures in a short time to avoid serious accidents and fires.

Measurement of the "phase-zero" loop is carried out during acceptance testing of equipment at the request of controlling organizations or periodically - once every 3 years.
When measuring the loop resistance "phase-zero", "phase-phase", the device simultaneously measures the active, reactive and impedance of the loop, and also calculates the predicted short-circuit current without disabling the line protection. This is necessary to check the correctness of the set nominal value of the short-circuit protection element (circuit breaker or fuse) and determine the timely operation of this protection. The body of the device is equipped with magnetic holders, which allows, if necessary, to quickly mount the device on steel surfaces, including those with paint and varnish coatings.

Peculiarities:

  • automatic selection of measurement ranges;
  • shock-resistant, dust- and moisture-proof case with a magnetic holder. Degree of protection IP54;
  • automatic switch to power-saving mode 2.5 minutes after the end of measurements;
  • liquid crystal display;
  • indication of the state of the internal power supply;
  • battery protection system from overcharging;
  • protection against incorrect inclusion;
  • high noise immunity;
  • memory for 10,000 measurements, connection with a computer.


Specifications:


AC voltage measurement

Measurement range of the effective voltage value, V

from 10.0 to 450.0

Operating frequency range, Hz

from 45 to 65

Measurement of active, reactive and total resistance of the loop "phase-zero", "phase-phase"

Measurement ranges of active, reactive and total resistances of the loop "phase-zero", "phase-phase", Ohm

0.01 to 9.99

10.0 to 99.9

from 100 to 200

Measuring ranges of loop impedance "phase-zero", "phase-phase", Ohm   

0.01 to 9.99

from 10.0 to 99.9

 from 100 to 300

Operating voltage range, V

from 180 to 450

Calculation of the predicted short circuit current

Calculation range of the predicted short-circuit current of the "phase-zero" circuit, kA

from 0 to 22 kA

Calculation range of the predicted short-circuit current of the phase-to-phase circuit, kA

from 0 to 38 kA

DC electrical resistance measurement (metal bonding)

Resistance measurement limits, Ohm

0.01 to 999

Current in the measuring circuit for resistances not more than 10 Ohm, mA

at least 200

Functionality:

  • measurement of effective values of alternating voltage;
  • measurements of active, reactive, impedance of the loop "phase-zero", "phase-phase";
  • calculation of predicted short circuit current;
  • measurement of metal bond resistance.


ООО «ТД «Радио-Сервис» / “Radio-Service”, JSC.

The company "Radio-Service" offers a wide range of electrical measuring instruments for route-finding equipment of various prices, used in various fields of activity. The good quality and affordable price of our products have allowed us to take a strong position in the Russian market.

The instruments we produce include:

  • megaohmmeters;
  • ground resistance meters;
  • loop resistance meters;
  • RCD parameters meters;
  • voltammeters;
  • route finders;
  • marker detectors.

No reviews found